Manufacturer
|
Amphenol |
Series
|
T5100 |
Sensing Method
|
Gold-plated optics, Non-dispersive infrared (NDIR) absorbsion, Patented ABC Logic self calibration algorithm |
CO2 Measurement Range
|
(0 ppm = 0 V, 4 mA), 0 to 2000ppm |
CO2 Accuracy
|
±30 ppm or 3% of the reading shown, whichever is higher * |
Power Supply Requirement
|
18 to 42 VDC,polarity protected*AHRAE — regulation 62 states maximum indoor CO2 level of 1000 ppm |
Power Supply Consumption
|
Typical 0.7 W at nominal voltage of 24V AC RMS |
Temperature Dependance
|
0.2% FS per °C (±0.11% per °F) |
Stability
|
<2% of FS over life of sensor (15 years) |
Pressure Dependence
|
0.135% of reading per mm Hg |
Certification
|
CE EMC, RoHS, REACH and WEEE compliant |
Signal Update
|
Every 5 seconds |
CO2 Warm-up Time
|
<2 minutes (operational), 10 minutes (maximum accuracy) |
Operating Conditions
|
0 to 95% RH, non-condensing, 32°F to 122°F (0°C to 50°C) |
Storage Conditions
|
-40°F to 158°F (-40°C to 70°C) |
Flammability Classification
|
UL94 5VA |
Output
|
Field selectable voltage or current, Voltage only (0-10 or 0-5V)- Current only (4-20 mA) |
Analog (CO2)
|
0 to 5 V, or 0 to 10 V jumper selectable (100 Ω output impedance) Or 4 to 20 mA (RL maximum 500 Ω), Digital to analog error ±1%, Voltage and current outputs are not available simultaneously |