Manufacturer
|
Amphenol |
Series
|
T5100 |
Sensing Method
|
Gold-plated optics, Non-dispersive infrared (NDIR) absorbsion, Patented ABC Logic self calibration algorithm |
CO2 Measurement Range
|
(0 ppm = 0 V, 4 mA), 0 to 2000ppm |
CO2 Accuracy
|
±30 ppm or 3% of the reading shown, whichever is higher * |
Active Temperature Accuracy/Range
|
±1°C from 15-30°C (±1.8°F from 59 to 86°F), 0-50°C (32-122°F) |
Power Supply Requirement
|
18 to 42 VDC,polarity protected*AHRAE — regulation 62 states maximum indoor CO2 level of 1000 ppm |
Power Supply Consumption
|
Typical 0.7 W at nominal voltage of 24V AC RMS |
Temperature Dependance
|
0.2% FS per °C (±0.11% per °F) |
Stability
|
<2% of FS over life of sensor (15 years) |
Pressure Dependence
|
0.135% of reading per mm Hg |